Doepke Type-B+ Heat Pump RCCB 40A 2P 30mA 6kA

£198.60 (Inc. VAT)
£165.50 (Ex. VAT)
Weight:
300.00 Grams
Current Stock:
Adding to cart… The item has been added

The Doepke DFS 2 040-2/0,03-HP RCCB is suitable for heat pumps, meeting manufacturer requirements including Vaillant. 

Type B+: Capable of detecting AC, pulsating DC, and smooth DC residual currents up to 20 kHz

An RCCB provides residual current protection, overcurrent protection should be provided with a suitably sized MCB. 

  
Series DFS 2 HP
Number of poles 2
Residual current type B+
Max current (AC) 40 A
Rated residual current (IΔn) 0.03 A (30 mA)
Short-time delayed true
Selective false
Min. Operating voltage test circuit 150 V
Max. Operating voltage test circuit 250 V
Minimum rated operating voltage (Type A/AC operation) 0 V AC
Minimum rated operating voltage (Type B operation) 50 V AC
Non-trip time 13 ms
Tripping frequency range 0 Hz to 20 kHz
Maximum disconnection times 1 · IΔn: ≤ 300 ms; 5 · IΔn: ≤ 40 ms
Technical changes reserved 2025_07_26

Documentation 

Datasheet

Installation Manual

Doepke Heat Pump RCD Technical Note

Doepke Heat Pump RCD Overview